Cycle and reaction times
5.2 Cycle time
CPU 31xC and CPU 31x, Technical Data
5-2 Manual, 01/2006 Edition, A5E00105475-06
Meaning of the term cycle time
The cycle time represents the time that an operating system needs to execute a program,
that is, one OB 1 cycle, including all program sections and system activities interrupting this
cycle. This time is monitored.
Time slice model
Cyclic program processing, and therefore user program execution, is based on time shares.
To clarify these processes, let us assume that every time share has a length of precisely
1 ms.
Process image
During cyclic program processing, the CPU requires a consistent image of the process
signals. To ensure this, the process signals are read/written prior to program execution.
Subsequently, the CPU does not address input (I) and output (Q) address areas directly at
the signal modules, but rather accesses the system memory area containing the I/O process
image.
Sequence of cyclic program processing
The table and figure below show the phases in cyclic program processing.
Table 5-1 Cyclic program processing
Step Sequence
1 The operating system initiates cycle time monitoring.
2 The CPU copies the values of the process image of outputs to the output modules.
3 The CPU reads the status at the inputs of the input modules and then updates the
process image of inputs.
4 The CPU processes the user program in time shares and executes program instructions.
5 At the end of a cycle, the operating system executes queued tasks, for example, loading
and deleting blocks.
6 The CPU then returns to the start of the cycle, and restarts cycle time monitoring.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)