Time switch based on the S7-300/400 CPUs with simple HMI system
including radio-controlled clock connection
Rev. B - final 19.07.2002 32/84
Copyright © Siemens AG 2005 All rights reserved
BID21669756_Zeitschaltuhr_einfach_DOKU_v20_e.doc
Fig 4-4 Configuration “one-day time switch”
Basic data/parameterizability:
RAM requirements:
day: 760 bytes
Instance DB: 52 bytes
The parameter “Time_To_Check“ is a structure of the “day_udt“ (UDT1)
type. It contains:
Start hour, start minute, start second summarized as “starttime” with
structure of the “times” (UDT6) type
End hour, end minute, end second summarized as “endtime” with
structure of the “times” (UDT6) type
4.3.3 Seven-day time switch
The block for the seven-day time switch “week” FB121 is parameterized as
illustrated in the figure below. Data block DB121 is used as instance data
block:
Fig 4-5 Configuration “seven-day time switch”