8.4 System status lists for PROFINET IO
S7-400H
102 System Manual, 03/2012, A5E00267695-11
SSL-ID PROFINET IO PROFIBUS DP Applicability
W#16#0D91 Yes
Parameter adr1 changed
No, external interface
Yes Module status information of all modules
in the specified rack/station
W#16#0696 Yes, internal interface
No, external interface
No Module status information of all
submodules on an internal interface of a
module using the logical address of the
module, not possible for submodule 0 (=
module)
W#16#0C75 Yes, parameter adr1
changed
Yes Communication status between the fault-
tolerant system and a switched DP
slave/PN device
W#16#0C96 Yes, internal interface
No, external interface
Yes, internal interface
No, external interface
Module status information of a
submodule using the logical address of
this submodule
W#16#xy92 No
Replacement: SSL-ID
W#16#0x94
Yes Rack/stations status information
Replace this system status list with the
system status list with ID W#16#xy94 in
PROFIBUS DP, as well.
W#16#0x94 Yes, internal interface
No, external interface
Yes, internal interface
No, external interface
Rack/station status information
Detailed information
For detailed descriptions of the individual system status lists, refer to the manual
System
Software for S7-300/400 System and Standard Functions
.