Assembly of a CPU 41x–H   
5.7 Multi Point Interface MPI/DP (X1) 
  S7-400H 
70  System Manual, 03/2012, A5E00267695-11 
5.7  Multi Point Interface MPI/DP (X1) 
Connectable devices   
You can, for example, connect the following devices to the MPI: 
●  Programming devices (PG/PC) 
●  Operating and monitoring devices (OPs and TDs) 
●  Further SIMATIC S7 controllers 
Various compatible devices take the 24 V supply from the interface. This voltage is non-
isolated. 
PG/OP–CPU communication   
A CPU is capable of handling several online connections to PGs/OPs in parallel. By default, 
however, one of these connections is always reserved for a PG, and one for an OP/HMI 
device.  
CPU–CPU communication   
CPUs exchange data by means of S7 communication. 
For additional information, refer to the 
Programming with STEP 7
 manual. 
Connectors   
Always use bus connectors with an angular cable outlet for PROFIBUS DP or PG cables to 
connect devices to the MPI (see 
Installation Manual
). 
MPI as DP interface 
You can also parameterize the MPI for operation as DP interface. To do so, reparameterize 
the MPI under STEP 7 in the SIMATIC Manager. You can configure a DP segment with up to 
32 slaves.