EasyManua.ls Logo

Siemens SIMATIC S7-400H - Calculating the Cycle Time

Siemens SIMATIC S7-400H
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S7-400 cycle and response times
19.2 Calculating the cycle time
S7-400H
358 System Manual, 03/2012, A5E00267695-11
19.2 Calculating the cycle time
Extending the cycle time
The cycle time of a user program is extended by the factors outlined below:
Time-based interrupt processing
Hardware interrupt processing (see also section Interrupt response time (Page 379))
Diag
nostics and error p
rocessing (see also section Example of calculation of the interrupt
response time (Page 381))
Comm
unication via MPI or the integrate
d PROFINET interface and CPs connected by
means of the communication bus
(e.g.: Ethernet, Profibus, DP) as a factor in communication load
Special functions such as operator control and monitoring of tags
or the block status
Transfer and deletion of blocks, compressing of the user program memory
Runtime of signals using the synchronization cable
Influencing factors
The table below shows the factors influencing the cycle time.
Table 19- 2 Factors influencing cycle time
Factors Remark
Transfer time for the process
output image (POI) and process
input image (PII)
See tables from 19-3 onwards
User program execution time This value is calculated based on the execution times of the
various statements (see the
S7-400 statement list
).
Operating system execution time
at the cycle control point
See Table 19-7
Extension of cycle time due to
communication load
You configure the maximum permitted communication load on
the cycle as a percentage in STEP 7 (
Programming with STEP 7
manual). See section Communication load (Page 366).
Load on cycle times due to
interrupts
Interrupt requests can always stop user program execution. See
Table 19-8

Table of Contents

Other manuals for Siemens SIMATIC S7-400H

Related product manuals