Using I/Os in S7–400H 
  13.4 Connecting redundant I/O to the PROFIBUS DP interface 
S7-400H 
System Manual, 03/2012, A5E00267695-11 
193 
Library V5.x  Library V4.x  Library V3.x  Module   Order number 
AI 6xTC 16Bit iso, 6ES7331-7PE10-0AB0  6ES7331-7PE10-0AB0 
X    X 
Notice: These modules must only be used with redundant encoders. 
You can use this module with Version 3.5 or higher of FB 450 "RED_IN" in the 
library "Redundant IO MGP" and Version 5.8 or higher of FB 450 "RED_IN" in 
the library "Redundant IO CGP" V50. 
Observe the following when measuring temperatures by means of 
thermocouples and parameterized redundancy: 
The value specified in "Redundancy" under "Tolerance window" is always based 
on 2764.8 °C. For example, a tolerance of 27 °C is checked if "1" is entered, or a 
tolerance of 138 °C is checked if "5" is entered.  
A firmware update is not possible in redundant mode. 
Online calibration is not possible in redundant mode. 
Use in voltage measurement 
  The "wire break" diagnostics function in HW Config must not be activated 
when operating the modules with thermocouples. 
Use in indirect current measurement 
  Due to the maximum voltage range +/- 1 V, the indirect current measurement 
can be carried out exclusively via a 50 ohm resistor. Mapping that conforms 
to the system is only possible for the area +/- 20 mA. 
AI 4x15Bit [EEx ib]  6ES7331-7RD00-0AB0 X    X 
You cannot use the module for applications in hazardous areas in redundant 
mode. 
It is not suitable for indirect current measurement. 
Use in direct current measurement 
  Suitable Zener diode: BZX85C6v2 
  Load capability of 4-wire transmitters: RB > 325 ohms  
determined for worst case: 1 input + 1 Zener diode at an S7 overshoot value 
24 mA to RB = (RE * I
max +
 U
z max
)/I
max
 
  Input voltage for 2-wire transmitters: Ue–2w < 8 V  
determined for worst case: 1 input + 1 Zener diode at an S7 overshoot value 
24 mA to Ue–2w = RE * I
max 
+ U
z max
 
Note: You can only connect 2-wire transmitters with a 24 V external supply or 4-
wire transmitters. The internal power supply for transmitters cannot be used in 
the circuit shown in figure 8-10, because this outputs only 13 V, and thus in the 
worst case it would supply only 5 V to the transmitter. 
AI 6x13Bit  6ES7 336–1HE00–0AB0 X    X 
F module in standard mode 
AI 8x0/4...20mA HART  6ES7 331–7TF01-0AB0 X  X  X 
A firmware update is not possible in redundant mode. 
Online calibration is not possible in redundant mode. 
See 
Distributed I/O Device ET 200M; HART Analog Modules
 manual