EasyManua.ls Logo

Siemens SIMATIC S7-400H - Page 352

Siemens SIMATIC S7-400H
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Synchronization modules
18.3 Selecting fiber-optic cables
S7-400H
352 System Manual, 03/2012, A5E00267695-11
Table 18- 3 Specification of fiber-optic cables for outdoor applications
Cabling Components required Specification
Installation cables for
outdoor applications
Installation cables for outdoor applications
1 cable with 4 cores per fault-tolerant system
Both interfaces in one cable
1 or 2 cables with several shared cores
Separate installation of the interfaces in order to
increase availability (reduction of common cause
factor)
Connector type ST or SC, for example, to match
other components; see below
Further specifications you may need to observe for
your plant:
UL approval
Halogen-free materials
Further specifications you may need to observe for
your plant:
Protection against increased mechanical stress
Protection against rodents
Water-proofing
Suitable for direct underground installation
Suitable for the given temperature ranges
Avoid splicing cables in the field. Use prefabricated
cables with pulling protection/aids in whiplash design,
including measuring log.
including patch cables for
indoor applications as required
1 cable with 4 cores per fault-tolerant system
Both interfaces in one cable
1 or 2 cables with several shared cores
Separate installation of the interfaces in order to
increase availability (reduction of common cause
factor)
Connector type ST or SC, for example, to match
other components; see below
Further specifications you may need to observe for
your plant:
UL approval
Halogen-free materials
Avoid splicing cables in the field. Use prefabricated
cables with pulling protection/aids in whiplash or
breakout design, including measuring log.
A cable junction is required
between the indoor and
outdoor area
see Figure 18-2
Patch cable for indoor
applications
Connector type LC on ST or SC, for example, to
match other components

Table of Contents