Technical data
20.1 Technical specification of the CPU 412–5H PN/DP; (6ES7 412-5HK06–0AB0)
S7-400H
System Manual, 03/2012, A5E00267695-11
385
FCs Maximum 3000
Number range 0 - 7999
Size
Maximum 64 KB
SDBs Maximum 2048
Address ranges (I/O)
Total I/O address range 8 KB/8 KB
of those distributed
Including diagnostic addresses, addresses for I/O
interfaces, etc.
MPI/DP interface 2 KB/2 KB
DP interface 4 KB/4 KB
PN interface 8 KB/8 KB
Process image 8 KB / 8 KB (configurable)
Default
256 bytes/256 bytes
Number of process image partitions
Maximum 15
Consistent data
Max. 244 bytes
Access to consistent data in the process image Yes
Consistent data via PROFIBUS
Via integrated PROFINET interface
Max. 244 bytes
Max. 1024 bytes
Digital channels Maximum 65536/maximum 65536
of those central
Maximum 65536/maximum 65536
Analog channels Maximum 4096/maximum 4096
of those central
Maximum 4096/maximum 4096
Configuration
Central controllers/expansion units Maximum 2/20
Multicomputing No
Number of plug-in IMs (total) Maximum 6
IM 460
Maximum 6
IM 463–2
Maximum 4, in stand-alone mode only
Number of DP masters
integrated
2
Via CP 443–5 Ext.
Maximum 10
Number of plug-in S5 modules via adapter casing
(in the central controller)
None
Operable function modules and communication
processors
FM, CP (point-to-point)
see Appendix Function modules and
communication
processors supported by the
S7-400H (Page 457)
Limite
d by the number of slots and con
nections
CP 441
Limited by the number of connections