Technical data
20.1 Technical specification of the CPU 412–5H PN/DP; (6ES7 412-5HK06–0AB0)
S7-400H
System Manual, 03/2012, A5E00267695-11
389
Functionality
MPI
Yes
PROFIBUS DP
DP master
1st interface in MPI mode
Utilities
PG/OP communication
Yes
Routing
Yes
S7 communication
Yes
Global data communication
No
S7 basic communication
No
Transmission rates
Maximum 12 Mbps
1st interface in DP master mode
Utilities
PG/OP communication
Yes
Routing
Yes
S7 communication
Yes
Global data communication
No
S7 basic communication
No
Constant bus cycle time
No
Isochronous mode
No
SYNC/FREEZE
No
Enable/disable DP slaves
No
Direct data exchange (cross-traffic)
No
Transmission rates Maximum 12 Mbps
Number of DP slaves Maximum 32
Number of slots per interface Maximum 544
Address range Maximum 2 KB inputs / 2 KB outputs
User data per DP slave Maximum 244
Maximum 244 bytes inputs
Maximum 244 bytes outputs
Maximum 244 slots
Maximum 128 bytes per slot
Note:
The total of input bytes across all slots may not exceed 244.
The total of output bytes across all slots may not exceed 244.
The address range of the interface (maximum 2 KB inputs / 2 KB outputs) must not be exceeded
in total across all 32 slaves.