Technical data   
20.1 Technical specification of the CPU 412–5H PN/DP; (6ES7 412-5HK06–0AB0) 
  S7-400H 
392  System Manual, 03/2012, A5E00267695-11 
PROFINET IO 
PNO ID (hexadecimal)  Vendor ID: 0x002A 
Device ID: 0x0102 
Number of integrated PROFINET IO controllers  1 
Number of PROFINET IO devices that can be 
connected 
256 
Number of connectable IO devices for RT 
of which are in line 
256 
256 
Shared Device, supported  No 
Address range  Maximum 8 KB inputs/outputs 
Number of submodules  Maximum 8192 
Mixed modules count twice 
Maximum user data length, including user data 
qualifiers 
1440 bytes 
Maximum user data consistency, including user 
data qualifiers 
1024 bytes 
Send clock cycles   250 µs, 500 µs, 1 ms, 2 ms, 4 ms 
Update Time  250 μs, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 
32 ms, 64 ms, 128 ms, 256 ms, and 512 ms 
The minimum value depends on the 
communication slice set for PROFINET IO, the 
number of IO devices, and the amount of 
configured user data. 
Maximum user data length   1024 bytes per address range 
Maximum consistency of user data  1024 bytes per address range 
S7 protocol functions   
  PG functions 
Yes 
  OP functions 
Yes 
IRT (Isochronous Real Time)  No 
Prioritized startup 
Accelerated (ASU) and Fast Startup Mode (FSU) 
No 
Tool change  No 
Changing an IO device without Micro Memory 
Card or PG 
Yes 
4th and 5th interface 
Designation of the interfaces  IF1, IF2 
Type of interface  Plug-in synchronization module (FOC) 
Usable interface module  Synchronization module IF 960 (only in 
redundant mode; in stand-alone mode the 
interface remains free/covered) 
Length of the synchronization cable  Max. 10 km