Technical data
20.4 Technical specifications of the CPU 417–5H PN/DP; (6ES7 417-5HK06–0AB0)
S7-400H
System Manual, 03/2012, A5E00267695-11
421
Address ranges (I/O)
Total I/O address range 16 KB/16 KB
of those distributed
Including diagnostic addresses, addresses for I/O
interfaces, etc.
MPI/DP interface 2 KB/2 KB
DP interface 8 KB/8 KB
Process image 16 KB/16 KB (configurable)
Default
1024 bytes/1024 bytes
Number of process image partitions
Maximum 15
Consistent data via PROFIBUS
Via integrated PROFINET interface
Max. 244 bytes
Max. 1024 bytes
Access to consistent data in the process image Yes
Digital channels Maximum 131072/
Maximum 131072
of those central
Maximum 131072/
Maximum 131072
Analog channels Maximum 8192/
Maximum 8192
of those central
Maximum 8192/
Maximum 8192
Configuration
Central controllers/expansion units Maximum 2/20
Multicomputing No
Number of plug-in IMs (total) Maximum 6
IM 460
Maximum 6
IM 463–2
Maximum 4, in stand-alone mode only
Number of DP masters
integrated
2
Via CP 443–5 Ext.
Maximum 10
Number of plug-in S5 modules via adapter casing
(in the central controller)
None
Operable function modules and communication
processors
FM, CP (point-to-point)
see Appendix Function modules and
communication
processors supported by the
S7-400H (Page 457)
Limite
d by the number of slots and con
nections
CP 441
Limited by the number of connections
PROFIBUS and Ethernet CPs, including CP
443–5 Extended
Maximum 14, of which max. 10 CPs as DP
masters
Connectable OPs 63