Stand-alone operation   
 
  S7-400H 
450  System Manual, 03/2012, A5E00267695-11 
5.  Reconfigure the communication connections. 
6.  Carry out all changes required, such as the insertion of one-sided I/Os. 
For information on how to configure the project refer to the Online Help. 
Changing the operating mode of a fault-tolerant CPU   
The procedure for changing the operating mode of a fault-tolerant CPU differs depending on 
the operating mode you want to switch to and the rack number configured for the CPU: 
Changing from redundant to stand-alone mode 
1.  Remove the synchronization modules 
2.  Remove the CPU. 
3.  Set rack number 0 on the CPU. 
4.  Install the CPU. 
5.  Download a project with the stand-alone configuration to the CPU. 
Changing from stand-alone mode to redundant mode, rack number 0 
1.  Insert the synchronization modules into the CPU. 
2.  Run an unbuffered power cycle, for example, by removing and inserting the CPU, or 
download a project to the CPU in which it is configured for redundant mode. 
Changing from stand-alone mode to redundant mode, rack number 1 
1.  Set rack number 1 on the CPU. 
2.  Install the CPU. 
3.  Insert the synchronization modules into the CPU.