Siemens AG 2001 All rights reserved 6FC5198–jAB40
1–172
SINUMERIK 840C / SIMODRIVE 611–D (DA)
165034 Conversion has not been switched on OK softkey
Loading drive machine data
Illegal data in drive
–
Repeat operation
Applies as from SW 5.4.
165035 MD for motor/p section comb. not preset OK softkey
Drive MD, axis (FDD): select motor
Drive is not parameterized
There are no standard data for this motor/PS combination
Select a different motor or motor from another manufacturer
165036 Not a valid drive number OK softkey
Saving and loading MD of one individual drive
Selected function is not executed
An illegal drive number has been entered
Enter a legal drive number
165037 Boot file drive n. not saved OK softkey
Saving BOOT for one or all drives
Current drive status lost after next reset
No communication with drive
Save BOOT configuration, NCK reset, repeat operation
165038 Drive configuration has not been loaded OK softkey
Loading user drive machine data
No connection to drives
The loaded MD file does not contain a configuration
Load file with configuration data
165039 No communication to the digital drives OK softkey
Saving, loading drive MD
Function is not executed
The stated configuration is accepted
Save BOOT configuration, NCK reset, repeat operation
165040 Only user configuration can be changed OK softkey
Softkey “Configure memory”
Function is not performed
Standard or on-line configuration selected accidentally.
Select user setting under “File functions”
Applies as from SW 4
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Scan
Effect
Explanation
Remedy
Scan
Effect
Explanation
Remedy
Scan
Effect
Explanation
Remedy
Scan
Effect
Explanation
Remedy
Scan
Effect
Explanation
Remedy
Note
1 Alarms
1.5.1 Alarm description