What to do if Siemens Engine fan does not run anymore?
- MMichael BurnettAug 4, 2025
If the Siemens Engine fan stops running, there are several potential causes. It could be due to: * No line voltage, a line failure, or under/overvoltage: In this case, check the line voltage. * An earth fault: Inspect the motor connection and line voltage. * A short circuit winding: The fan may need to be replaced. * The thermal motor protection has triggered because the motor is overheated: Ensure free air passages, and remove any obstructions. Also, check the temperature of the supply air and the voltage. * The impeller is blocked or dirty: Switch off the power, ensure safe isolation, remove the safety grille, clear any foreign objects or dirt, and then remount the grille. Refer to the chapter on “Start-up” for further instructions.