Converter data sheets and characteristics
4.2 Water cooling
Commissioning instructions for SIMOTICS M-1PH8 Premium Performance
66 Commissioning Manual, 10/2014, 610.40106.40
Additional parameterization
Booksize 60 A
400 V
480 V
Motor type selection
p300
1
1
Line resistance
p352
0.0461
0.0461
Current controller adaptation, starting point
KP
p391 0 0
Current controller adaptation, starting point
KP adapted
p392 25 25
Current controller adaptation, P gain adapta-
tion
p393 40 40
Current limit
p640
81
81
Maximum rotation speed
p1082
24,000
24,000
Torque limit, upper/motoring
p1520
64
64
Torque limit, lower/regenerative
p1521
-64
-64
Power limit, motoring
p1530
34.8
37.5
Power limit, regenerative
p1531
-34.8
-37.5
Maximum field-generating current
p1603
0
0
Pulse frequency setpoint
p1800
4
4
Modulator configuration
p1810
"&H800"
"&H800"
Current controller P gain
p1715
6
6
Reference speed reference frequency
p2000
24,000
24,000
Reference current
p2002
81
81
Reference torque
p2003
64
64
Hysteresis speed n_act > n_max
p2162
480
480