Terminal Module TM17 High Feature Unit Value
Leakage current in OFF state
μA max. 10 per channel
Output voltage drop
(I/O power supply to the output)
V
DC
0.5
Max. total current of the outputs (per group)
to 60 °C
to 50 °C
to 40 °C
A
DC
A
DC
A
DC
2
3
4
IEC enclosure specification IP20 degree of protection
Protective-conductor connection On the housing with M4/1.8 Nm screw
Weight kg 0.86
Approval UL and cULus
http://www.ul.com
File: E164110, Vol. 2, Sec. 9
1
The shortest pulses can be detected using the 1 μs filter; however, the 125 μs filter will provide
higher noise immunity.
Terminal Module TM17 High Feature
3.8 Technical data
TM15 / TM17 High Feature Terminal Modules
Manual, 11/2016 51