Connecting
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
41
:LGWK
DD
F
H G
&XWRXWLQWKH
FRQWUROFDELQHW
IRUWKHKHDW
VLQN
E
+HLJKW
G
Figure 3-6 Dimensions and drilling pattern, M250-2, PT
Table 3- 6 Power Module PM250-2, push-through
PM250-2 Power Dimensions Clearances
PT kW Heigh
t
Width Depth a b c d e top bottom lateral
mm
inch
226
8,90
126
4,96
165
6,50
103
4,06
106
4,17
188
7,04
9
0,35
88
3,46
100
3,94
100
3,94
0
0
FSA
without /
with filter
3
Fixing: M4 screws, Torque: 2.5 Nm / 22.1 lbf.in
mm
inch
315
12,40
154
6,06
165
6,50
147,5
5,81
134
5,28
188
7,04
10
0,39
117
4,61
100
3,94
100
3,94
0
0
FSB
without /
with filter
7,5
Fixing: M4 screws, Torque: 2.5 Nm / 22.1 lbf.in