Connecting
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
42 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Dimensions and drilling patterns of the Power Modules
:LGWK
+HLJKW
E
DF
Figure 3-7 Dimensions and drilling pattern PM260
Table 3- 7 Power Module PM260, IP20
PM260 Power Dimensions Clearances
IP20 kW Height Width Depth a b c top bottom lateral
mm
inch
511
20,12
275
10,83
195
7,68
419
16,5
235
9,3
11
0.43
100
3,94
100
3,94
30*
1,18*
FSD
without /
with filter
3
Fixing: M6 screws, Torque: 6 Nm / 53 lbf.in
mm
inch
634
24,96
350
13,78
307
12,09
598
23,54
300
11,81
11
0.43
100
3,94
100
3,94
0
0
FSF
without /
with filter
7,5
Fixing: M8 screws, Torque: 13 Nm / 115 lbf.in
*) up to 40 °C without any lateral clearance