4.5 Connecting the 24 V power supply
An external 24 V supply with an external overcurrent protection device is required for operating
the distributed inverter box.
9
9
Figure 4-3 Overcurrent protection device
Use an LV HRC fuse 6A GL/GG, 500 V.
Feed a 24 V cable through the floor of the cabinet
Cable entry (Page 16)
Connecting a 24 V cable
Connect the 24 V cable to terminal -XDL2 as follows:
-XDL2:10 → 24 V
-XDL2:29 → 0 V
Permissible cross-sections of the 24 V cable: 0.14 mm² … 2.5 mm²
&DEOHHQWU\
;'/
99
3(
Figure 4-4 24 V connection
Connection
4.5 Connecting the 24 V power supply
Distributed inverter box
Manual, 06/2018, A5E43491109B AB 17