Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
59
Power unit overload response
0 Reduce output current or output frequency
1 No reduction, shutdown when overload
2 Reduce I_output or f_output and f_puls
Reduce the pulse frequency (not using I2t)
12 I_output or f_output and automatic pulse
Automatic pulse frequency reduction
Power unit temperature alarm threshold [°C]
p0300 Motor type selection
0 No mo-
tor
1 Standard
induction
Motor code number selection
Number of motors connected in parallel
Rated motor efficiency [%]
Rated motor frequency [Hz]
Motor pole pair number, current (or calculated)
p0320 Motor rated magnetizing current/short-circuit
Maximum motor speed [rpm]
Maximum motor current [A]
Motor pole position identification current 1. Phase
Motor pole position identification current [A]
r0331 Actual motor magnetizing current/short-circuit
Automatic calculation of motor/control parameters
p0341 Motor moment of inertia [kgm²]
p0342 Ratio between the total and motor moment of
p0344 Motor weight (for thermal motor model) [kg]
Motor rated running-up time [s]
Motor excitation build-up time [s]
Motor de-excitation time [s]
Motor stator resistance, cold [Ω]
2 Encoderless con-
trol up to f = 0
2 Pumps and fans,
efficiency optimi-
p0501 Technological application (Standard Drive Con-
0 Constant load
(linear characteris-
1 Speed-dependent
load (parabolic
Technology application (Dynamic Drive Control)
0 Standard drive
(e.g. pump, fan)
1 Dynamic ap-
proach or revers-
5 Heavy starting (e.g. extruders, compres-
Selecting the system of units
Specific scaling, reference values
Specific scaling, parameter referred to p0514[0]
Specific scaling, parameter referred to p0514[1]
Specific scaling, parameter referred to p0514[9]
Bearing, code number selection
Load gear unit code number
Load gear unit maximum speed