EasyManua.ls Logo

Siemens SINAMICS G120P - Page 45

Siemens SINAMICS G120P
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Setting the control mode (P1300)
In our example it is assumed that your converter and the motor are new. As a result, a series of
preparatory steps are required, e.g. selecting the control mode. This is indicated by the parameter
number 1300. ‘V/f control with parabolic characteristic curve’ is defined by the factory setting.
Press OK to modify the parameter value CTRL MOD
The upper line shows the control mode associated with the actual parameter value below
Choose “V/f control for a parabolic characteristic and ECO” value by pressing UP or DOWN
Observe how the control mode name in the upper row changes accordingly
Press OK if the desired control mode is displayed
Selecting the line frequency (P100)
The next parameter sequence sets the line frequency of the region in which the motor is being used.
In our example, this is Europe.
Press OK to modify the parameter value EUR USA
Set 0 for Europe (50 Hz) (1 represents the US line frequency of 60 Hz)
Confirm the value by pressing OK
The screen will automatically display the next parameter in the commissioning sequence
The applicable line frequency
can also be found on your motor
rating plate (see chapter “Enter-
ing motor data”).
NOTE
OK
OK
OK
OK

Other manuals for Siemens SINAMICS G120P

Related product manuals