Activating emergency operation
Choose “Functions” in the project tree
Double-click “Emergency operation”
Emergency operation opens in the work area
Start the parameterization by clicking on the blue binector button next to “Activate emergency operation”
A list of relevant parameters opens
Select parameter r722 for DI 5 corresponding to the wiring example (see wiring example)
Close the window with OK
Define the setpoint source by opening the drop-down menu
Select “Fixed speed setpoint (p1015)”
Enter fixed setpoint: 1500 rpm