34
Operator Panels BOP-2 and IOP-2: Quick commissioning
If you want to adjust any flash-
ing value digit by digit (using the
UP and DOWN button might take
too long) continuously press the
OK button for longer than two
seconds. After releasing the but-
ton, you can change each single
digit by using the buttons OK
(move to next digit), ESC (move
to previous digit), UP (increase
value) and DOWN (decrease
value).
NOTE
1
2
3
4
5
1
3
2
4
5
P304 = MOT VOLT = motor voltage
P100 = EUR USA = standard IEC or NEMA
P305 = MOT CURR = motor rated current
P307 = MOT POW = motor rated power
P311 = MOT RPM = motor rated speed
P308 = MOT COS PHI = Rated Motor power factor
The line frequency has been set already
in the beginning of quick commissioning
(see page 31).
Entering motor data
In the next step, the converter is adjusted to the motor. The motor data can be found on the motor
rating plate. Please set the values according to the rating plate.
Press OK to edit the motor voltage stored under P304
The preset motor voltage of 400 volts is displayed
Keep the value and confirm by pressing OK
OK
OK
6
6