The diagram shows the method of attaching the grounding spider. Secure the clamps for the
grounding spider to the ball heads and in the cabinet.
Schematic diagram of ball head
Ball head
Ball head
Figure 9-1 Schematic diagram for attaching the grounding spider
9.3 Opening the device
The drive is equipped with a door interlocking system. Depending on the design, this is an
electromechanical door interlocking system or optionally a safety locking system.
The power unit doors can only be opened under the following conditions:
The DC link current is zero.
The firing pulses are disabled.
Voltages at the input and output sides are below a minimum value.
The circuit breakers are open.
Maintenance
9.3 Opening the device
SINAMICS GL150 6SL38503UM114PA0Z
106 Operating Instructions Rev.201910301420 MUSTER