EasyManua.ls Logo

Siemens SINAMICS GL150 - Transportation Procedures

Siemens SINAMICS GL150
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
Hard S1 materials include steel, for example.
Table 5-2 Tightening torques for screw terminals for copper cables without cable lug
1)
Screw type Set screws and
headless screws
Head screws with
slit
Head screws with
hexagon profile
nm in - lb nm in - lb nm in - lb
M2 - - -
M2.5 0.25 2.2 0.5 4.4 0.5 4.4
M3 0.3 2.7 0.6 5.3 0.6 5.3
M3.5 0.5 4.4 1.0 8.9 1.0 8.9
M4 0.8 7.1 1.3 11.5 1.3 11.5
M5 1.0 8.6 2.5 22.1 2.5 22.1
M6 1.3 11.5 3.0 26.6 3.5 31.0
M8 1.8 15.9 3.9 34.5 7.2 63.7
M10 - - 4.8 42.5 13 115
M12 - - - - 18 159.3
M16 - - - - 30 265.5
Observe the tightening torques of the terminal manufacturer and the test torques according to
DIN EN 60999-1, VDE 609-1
5.4 Screwing the transport units together
NOTICE
Material damage caused by mechanical pressure on components
Stress that occurs during transport may exert mechanical pressure on the components.
Material damage can result.
Line the cabinets up precisely with each other in order to avoid shearing forces when the
base units are screwed together.
Install the converter only on a level and horizontal surface.
Ensure that access to the holes in the bottom of the cabinets is unobstructed. Remove the
guard covers.
Mounting hardware
To screw the transport units together, you will need the following mounting hardware:
Self-adhesive sealing strips
Hexagon nut M8
Mounting
5.4 Screwing the transport units together
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions Rev.201910301420 MUSTER 71