EasyManua.ls Logo

Siemens SINAMICS GL150 - Cleaning

Siemens SINAMICS GL150
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 9-4 Replacing the backup battery
Note
Dispose of the battery in accordance with the applicable country-specific laws and regulations.
Set date and time
1. Using the "MENU" key, select the main menu of the AOP 30.
2. Using "F2", select the menu item "Commissioning/service". Confirm with "F5"
3. Using "F2", select the menu item "AOP30 settings". Confirm with "F5"
4. Using "F2", select the menu item "Set date/time". Confirm with "F5". Using "F2", select the
appropriate input location for date or time. Enter the actual value using the numerical keys.
5. Use "F5" to save the settings.
9.6 Cleaning
NOTICE
Damage caused by aggressive cleaning agents
Aggressive chemical agents can damage the electronics. This can result in malfunction.
Never use any type of chemical agent or liquid.
Only remove severe dirt and contamination after prior consultation with service experts for
the particular product.
Use a dry, clean, lint-free ESD cleaning cloth. Wipe all external parts of the rack with it. Make
sure that the dirt is not distributed, but actually removed by constant changes of the wiping
surface of the cloth. For significant levels of pollution and dirt, use an ESD cloth soaked in ethyl
alcohol (however, not so much that it drips from the cloth).
Maintenance
9.6 Cleaning
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions Rev.201910301420 MUSTER 115