Junction box
Screws of the front brackets
Rear fixing screws
Figure 9-2 Replacing the fan
1. Open the cover of the junction box and remove the fan cables.
2. Remove the front M8 screws for the brackets .
3. Loosen the rear M8 fastening screws for the fan.
4. Pull out the fan and remove it from the converter.
Eyebolts can be fitted on top of the fan so that it can be lifted out of the converter more easily.
CAUTION
Injury due to a falling fan
The fans are very heavy (> 50 kg).
If incorrectly handled, fans can fall and result in injury and material damage.
Please take special care when removing the fans from the converter.
Installing the fan
1. Insert the new fan.
2. Move the fan onto the rear screws . Align the fan.
3. Insert the front screws M8 . Tighten the screws with a torque of 13 Nm.
4. Tighten the rear screws M8 (tightening torque: 13 Nm).
Maintenance
9.5 Maintenance
SINAMICS GL150 6SL38503UM114PA0Z
112 Operating Instructions Rev.201910301420 MUSTER