Activity Available/performed?
Cabinet operation from a higher-level control system / control room.
The control cables are connected in accordance with the interface assignment and
the shield is connected.
To prevent interference, the control cables are routed separately away from the power
cables.
The relevant EMC directives have been taken into account (Chapter "Electrical
connection")
DRIVE-CLiQ cables All DRIVE-CLiQ cables are correctly connected.
The permissible cable lengths are complied with.
("S120
Commissioning Manual, Rules for wiring with
DRIVE-CLiQ"
)
("S120 Equipment Manual for Booksize Power Units,
DRIVE-CLiQ Cabinet Gland" and "S120 Equipment
Manual for Booksize Power Units, DRIVE-CLiQ Cou‐
pling")
Optional components
CBC10 Communication Board The supplied CBC10 is installed in the factory in the
option slot of the Control Unit.
(S120 Cabinet Modules / Options / G20, Commu‐
nication Board CBC10 Manual).
CBE20 Communication Board The supplied CBC20 is installed in the factory in the
option slot of the Control Unit.
Remove the CBE20 in a no-current state and note
down
the MAC address. Install the CBE20 into the
option slot again.
("SINAMICS S120 Cabinet Modules / Options /
G33, Communication Board CBC20" Manual).
TM150 Temperature Sensor Mod‐
ule
A maximum of 12 temperature sensors (PT100,
PT1000, KTY84, PTC, bimetallic NC contact) are
connected to the TM150 Terminal Module.
("SINAMICS S120 Cabinet Modules / Options / G51
to G54, Temperature Sensor Module TM150" Man‐
ual).
Safety license for 1 to 5 axes The safety licenses are activated.
("SINAMICS
S120 Cabinet Modules / Options / K01
to K05, Safety License for 1 to 5 axes).
Sensor Module
SMC10
The correct encoders are connected to the SMC10
Sensor Module.
("SINAMICS S120 Cabinet Modules / Options / K
46,
Sensor Module Cabinet-Mounted SMC10" Man‐
ual).
SMC20
Sensor Module
The correct encoders are connected to the SMC10
Sensor Module.
("SINAMICS S120 Cabinet Modules / Options / K
48, Sensor Module Cabinet-Mounted SMC20" Man‐
ual).
Checklists and forms
C.2 Electrical installation: Checklist
Applications for Cabinet Modules, liquid cooled
148 Operating Instructions, 04/2015, A5E35974555A