Activity Available/performed?
SMC30
Sensor Module
The correct encoders are connected to the SMC10
Sensor Module.
("SINAMICS S120 Cabinet Modules / Options / K
50,
Sensor Module Cabinet-Mounted SMC30" Man‐
ual).
VSM10 Voltage Sensing Module
Cabinet-Mounted
To commission the function, the permanent-mag‐
net
synchronous machine without encoder must be
input and "Flying restart" activated with p1200.
("SINAMICS S120 Cabinet Modules / Options / K
51, Voltage Sensing Module Cabinet-Mounted
VSM10" Manual).
Fan power supply Voltages 1 AC 230 V and 24 V DC are fed in exter‐
nally.
("SINAMICS S120 Cabinet Modules / Options / K
70, Fan Power Supply" manual).
Auxiliary power generation in the
Line Connection Module
The phase is connected to the correct transformer
tap.
The correct voltage assignment is complied with.
("SINAMICS S120 Cabinet Modules / Options /
K76, Auxiliary Power Generation in the Line Con‐
nection Module" Manual).
Terminal Module TM54F The connection has been correctly established.
("SINAMICS S120 Cabinet Modules / Options /
K87, Terminal Module TM54F" manual).
Safe Brake Adapter SBA 230 V AC To control the brake, a connection is established
between -X14 on the Safe Brake Adapter and the
holding brake.
("SINAMICS S120 Cabinet Modules / Options /
K88, Safe Brake Adapter SBA AC 230 V" Manual)
Operation in an IT supply system The monitoring of the surge arresters and the up‐
stream fuses is connected to terminal ‑X700.
("SINAMICS S120 Cabinet Modules / Options /
L21, Operation on an IT Supply System" Manual).
Circuit breaker in withdrawable unit
design
The feedback signal contact is wired.
("SINAMICS S120 Cabinet Modules / Options /
L25,
Circuit Breaker in a Withdrawable Unit Design"
Manual).
Output-side circuit breaker The control is parameterized.
("SINAMICS S120 Cabinet Modules / Options /
L34, Output-Side Circuit Breaker" Manual).
Current transformer upstream of
the main switch
The measuring connections of the current trans‐
formers are wired.
("SINAMICS S120 Cabinet Modules / Options /
L41, Current Transformer Before the Main Switch"
Manual).
Checklists and forms
C.2 Electrical installation: Checklist
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A 149