Parameter list
7.1 Introduction to parameters
SINAMICS V20 Inverter
120 Operating Instructions, 07/2012, A5E03728167
Data type
The data types available are shown in the table below.
U8 8-bit unsigned
U16 16-bit unsigned
U32 32-bit unsigned
I16 16-bit integer
I32 32-bit integer
Float 32-bit floating point number
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source) the following combinations are possible when creating BICO
interconnections:
BICO input parameter
CI parameter BI parameter
BICO output parameter U32 / I16 U32 / I32 U32 / Float U32 / Bin
CO: U8 √ √ - -
CO: U16 √ √ - -
CO: U32 √ √ - -
CO: I16 √ √ - -
CO: I32 √ √ - -
CO: Float √ √ √ -
BO: U8 - - - √
BO: U16 - - - √
BO: U32 - - - √
BO: I16 - - - √
BO: I32 - - - √
BO: Float - - - -
Legend:
√: BICO interconnection permitted
-: BICO interconnection not permitted
Scaling
Specification of the reference quantity with which the signal value will be converted
automatically.
Reference quantities, corresponding to 100 %, are required for the statement of physical
units as percentages. These reference quantities are entered in P2000 ... P2004.
In addition to P2000 ... P2004 the following normalizations are used:
● TEMP: 100 °C = 100 %
● PERCENT: 1.0 = 100 %
● 4000H: 4000 hex = 100 %