Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
127
Parameter Function Range Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
r0053.0...15 CO / BO: Active status
word 2
- - - - - U16 2
Displays second status word of inverter (in bit format).
Bit Signal name 1 signal 0 signal
00 DC brake active Yes No
01 |f_act| > P2167 (f_off) Yes No
02 |f_act| > P1080 (f_min) Yes No
03 Act. current |r0068| >= P2170 Yes No
04 |f_act| > P2155 (f_1) Yes No
05 |f_act| <= P2155 (f_1) Yes No
06 f_act >= setpoint (f_set) Yes No
07 Act. unfilt. Vdc < P2172 Yes No
08 Act. unfilt. Vdc > P2172 Yes No
09 Ramping finished Yes No
10 PID output r2294 == P2292 (PID_min) Yes No
11 PID output r2294 == P2291 (PID_max) Yes No
14 Download Data set 0 from OP Yes No
15 Download Data set 1 from OP Yes No
Notice: r0053 bit 00 "DC brake active" ==> see P1233
Note: See r2197 and r2198
r0054.0...15 CO / BO: Active control
word 1
- - - - - U16 3
Displays first control word of inverter (in bit format) and can be used to diagnose which commands are
active.
Bit Signal name 1 signal 0 signal
00 ON / OFF1 Yes No
01 OFF2: Electrical stop No Yes
02 OFF3: Fast stop No Yes
03 Pulse enable Yes No
04 RFG enable Yes No
05 RFG start Yes No
06 Setpoint enable Yes No
07 Fault acknowledge Yes No
08 JOG right Yes No
09 JOG left Yes No
10 Control from PLC Yes No
11 Reverse (setpoint inversion) Yes No
13 Motor potentiometer MOP up Yes No
14 Motor potentiometer MOP down Yes No
15 CDS Bit 0 (Hand / Auto) Yes No
Notice: r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
r0055.0...15 CO / BO: Active control
word 2
- - - - - U16 3
Displays additional control word of inverter (in bit format) and can be used to diagnose which commands
are active.