Parameter list   
7.2 Parameter list 
  SINAMICS V20 Inverter 
134  Operating Instructions, 07/2012, A5E03728167 
Parameter  Function  Range  Factory 
default 
Can be 
changed 
Scaling  Data 
set 
Data 
type 
Acc. 
Level 
Caution:  The input of rating plate data must correspond with the wiring of the motor (star / delta). This means, if 
delta wiring is used for the motor, delta rating plate data has to be entered. 
,(&0RWRU
'HOWDFRQQHFWLRQ 6WDUFRQQHFWLRQ
:
8
8
9
9
:
:
8
8
9
9
:
8
9
:
8
9
:
 
Note:  Following diagram shows a typical rating plate with the locations of the relevant motor data. 
 
P0305[0...2]    Rated motor current [A]  0.01 - 
10000.00 
1.86  C(1)  -  DDS  Float  1 
  Nominal motor current from rating plate. 
Dependency:  Changeable only when P0010 = 1 (quick commissioning). 
Depends also on P0320 (motor magnetization current). 
Note:  The maximum value of P0305 depends on the maximum inverter current r0209 and the motor type: 
Asynchronous motor : P0305_max = P0209 
It is recommended that the ratio of P0305 (rated motor current) and r0207 (rated inverter current) should 
not be lower than: (1 / 8) <= (P0305 / r0207) 
When the relation of the nominal motor current P0305 and half of the maximal inverter current (r0209) 
exceeds 1.5 an additional current derating is applied. This is necessary to protect the inverter from 
harmonic current waves.  
I
max,Inv
r0209
1.5 2.5
 
Default value is depending on inverter type and its rating data.