Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
165
Parameter Function Range Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
Note: P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
P1080[0...2] Minimum frequency [Hz] 0.00 -
599.00
0.00 C(1), U, T - DDS Float 1
Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The minimum
frequency P1080 represents a masking frequency of 0 Hz for all frequency target value sources e.g. AI,
MOP, FF, USS with the exception of the JOG target value source (analogous to P1091). Thus the
frequency band + / -P1080 is run through in optimum time by means of the acceleration / deceleration
ramps. Dwelling in the frequency band is not possible. Furthermore, an overshoot of the actual frequency
f_act upper minimum frequency P1080 is output by the signal function |f_act| > f_min.
Note: Value set here is valid both for clockwise and for anticlockwise rotation.
Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.
P1082[0...2] Maximum frequency [Hz] 0.00 -
599.00
50.00 C(1), T - DDS Float 1
Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value
set here is valid for both clockwise and anticlockwise rotation.
Furthermore, the monitoring function |f_act| >= P1082 (r0052 bit 10, see example below) is affected by this
parameter.
Example:
%LW

__
3
+]3
3
U
W
W
IBDFW
IBDFW
IBPD[
The maximum value of P1082 also depends on the nominal frequency: Max. P1082 = min (15*P0310,
599.0 Hz). As consequence P1082 can be affected if P0310 is changed to a smaller value. The maximum
frequency and the pulse frequency depending on each other. The maximum frequency affects the pulse
frequency according to the following table.
P1800
2 kHz 4 kHz 6 kHz 8 - 16 kHz
f
max
P1082 0 - 133.3 Hz 0 - 266.6 Hz 0 - 400 Hz 0 - 599.0 Hz
Dependency:
Example:
If P1082 is set to 350 Hz a pulse frequency from at least 6 kHz is necessary. If P1800 is smaller than 6
kHz the parameter is changed P1800 = 6 kHz.
The maximum output frequency of inverter can be exceeded if one of the following is active:
6OLSFRPSHQVDWLRQDFWLYH
)O\LQJUHVWDUWDFWLYH


IIIຘ
ำ
ำ

IIIຘ
3
3
3
3
U
U
3
3
3
3
3
PD[
PD[
PD[
PD[
VOLSPD[
VOLSQRP

Table of Contents

Other manuals for Siemens SINAMICS V20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS V20 Series and is the answer not in the manual?

Siemens SINAMICS V20 Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS V20 Series
CategoryDC Drives
LanguageEnglish

Related product manuals