Parameter list   
7.2 Parameter list 
  SINAMICS V20 Inverter 
186  Operating Instructions, 07/2012, A5E03728167 
Parameter  Function  Range  Factory 
default 
Can be 
changed 
Scaling  Data 
set 
Data 
type 
Acc. 
Level 
Example:  If a BICO connection is made between two parameters or alternatively using P0719 or P1000, the 'unit' of 
the parameters (standardized (Hex) or physical (i.e. Hz) values) may differ. SINAMICS implicitly makes an 
automatic conversion to the target value. 
P1070
y[Hz]
2000P
4000[Hex]
r2018[1]
  y[Hz] ⋅=
r2018
[0]
[1]
[2]
[3]
P2019
[0]
[1]
[2]
[3]
r0021
x[Hz] y[Hex]
x[Hex]
]Hex[4000
P2000[Hz]
r0021[Hz]
  y[Hex] ⋅=
8663='RQ
56
8663='RQ
56
 
Dependency:  When Quick Commissioning is carried out, P2000 is changed as follows: P2000 = P1082. 
Caution:  P2000 represents the reference frequency of the above mentioned interfaces. 
A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface. 
Unlike P1082 (Maximum Frequency) this limits the inverter frequency internally independent of the 
reference frequency. 
By modification of P2000 it will also adapt the parameter to the new settings. 
PZD
f (Hex)
f [Hz]
f_act f_act,limit
P1082
2000P
 % 100 
f(%)
 2000P
 4000(Hex) 
f(Hex)
  f[Hz] ⋅=⋅=
f_act,limit = min(P1082, f_act)
f (%)
$QDORJ
Normalization Limitation
6HWSRLQW
FKDQQHO
0RWRU
FRQWURO
 
Notice:  Reference parameters are intended as an aid to presenting setpoint and actual value signals in a uniform 
manner. 
This also applies to fixed settings entered as a percentage. 
A value of 100 % corresponds to a process data value of 4000H, or 4000 0000H in the case of double 
values. 
In this respect, the following parameters are available: 
Hz
V
A
Nm
P2000
P2001
P2002
P2003
kW
hp
P2004
f(P0100)
5HIHUHQFHIUHTXHQF\
5HIHUHQFHYROWDJH
5HIHUHQFHFXUUHQW
5HIHUHQFHWRUTXH
5HIHUHQFHSRZHU
 
Note:  Changes to P2000 result in a new calculation of P2004. 
P2001[0...2]    Reference voltage [V]  10 - 2000  1000  T  -  DDS  U16  3 
  Full-scale output voltage (i.e. 100 %) used over serial link (corresponds to 4000H). 
Example: 
P0771
r0026
x[V] y[Hex]
]Hex[4000
P2001[V]
r0026[V]
  y[Hex] ⋅=
$,
 
Note:  Changes to P2001 result in a new calculation of P2004.