Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
187
Parameter Function Range Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
P2002[0...2] Reference current [A] 0.10 -
10000.0
0.10 T - DDS Float 3
Full-scale output current used over serial link (corresponds to 4000H).
Example: If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. A) values) may differ. In this case an automatic conversion to the target value is made.
[0]
[1]
[2]
[3]
r0027
x[A] y[Hex]
]Hex[4000
P2002[A]
r0027[A]
y[Hex] =
)LHOGEXV
3
Dependency: This parameter is influenced by automatic calculations defined by P0340.
Note: Changes to P2002 result in a new calculation of P2004.
P2003[0...2] Reference torque [Nm] 0.10 -
99999.0
0.75 T - DDS Float 3
Full-scale reference torque used over the serial link (corresponds to 4000H).
Example: If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. Nm) values) may differ. In this case an automatic conversion to the target value is made.
P2051
[0]
[1]
[2]
[3]
r0080
x[Nm] y[Hex]
]Hex[4000
P2003[Nm]
r0080[Nm]
y[Hex] =
)LHOGEXV
Dependency: This parameter is influenced by automatic calculations defined by P0340.
Note: Changes to P2003 result in a new calculation of P2004.
P2004[0...2] Reference power 0.01 -
2000.0
0.75 T - DDS Float 3
Full-scale reference power used over the serial link (corresponds to 4000H).
Example: If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. kW / hp) values) may differ. In this case an automatic conversion to the target value is made.
3
>@
>@
>@
>@
U
@[H+>\@:N>[
@> +H[
3
U
\>+H[@
[>KS@
)LHOGEXV
RU
GHSHQGLQJRQ3
P2010[0...1] USS / MODBUS
baudrate
6 - 12 8 U, T - - U16 2
Sets baud rate for USS / MODBUS communication.
6 9600 bps
7 19200 bps
8 38400 bps
9 57600 bps
10 76800 bps
11 93750 bps
12 115200 bps