Parameter list 
  7.2 Parameter list 
SINAMICS V20 Inverter 
Operating Instructions, 07/2012, A5E03728167 
207 
Parameter  Function  Range  Factory 
default 
Can be 
changed 
Scaling  Data 
set 
Data 
type 
Acc. 
Level 
 
•  P2350 = 4 
This tuning only changes values of P and I and should be a quarter damped response. 
The option to be selected depends on the application but broadly speaking option 1 will give a good 
response, whereas if a faster response is desired option 2 should be selected. 
If no overshoot is desired then option 3 is the choice. For cases where no D term is wanted then option 4 
can be selected. 
The tuning procedure is the same for all options. It is just the calculation of P and D values that is different. 
After autotune this parameter is set to zero (autotune completed). 
P2354  PID tuning timeout 
length [s] 
60 - 65000 240  U, T  -  -  U16  3 
  This parameter determines the time that the autotuning code will wait before aborting a tuning run if no 
oscillation has been obtained. 
P2355  PID tuning offset [%]  0.00 - 
20.00 
5.00  U, T  -  -  Float  3 
  Sets applied offset and deviation for PID autotuning. 
Note:  This can be varied depending on plant conditions e.g. a very long system time constant might require a 
larger value. 
P2360[0...2]    Enable cavitation 
protection 
0 - 2  0  U, T  -  DDS  U16  2 
  Cavitation protection enabled. 
Will generate a fault / warning when cavitation conditions are deemed to be present. 
7
 
U
ಹ
!
)HHGEDFNIORZ
SUHVVXUHVHQVRU
7ULSOHYHO
3,'6FDOHGIHHGEDFN
>@
6WDWXVZRUGELW3,'PLQLPXPOLPLWUHDFKHG
6WDWXVZRUGELW3,'PD[LPXPOLPLW
UHDFKHG
6WDWXVZRUGELW3,'LQYHUWHUUXQQLQJ
&DYLWDWLRQSURWHFWLRQHQDEOH
&DYLWDWLRQSURWHFWLRQGLVDEOHG
7ULJJHUFDYLWDWLRQZDUQLQJ$
7ULJJHUFDYLWDWLRQIDXOW)
1RWXVHG
Cavitation Protection Logic Diagram
&DYLWDWLRQSURWHFWLRQGHOD\
3,'HQDEOHGLVDEOH
&DYLWDWLRQ7KUHVKKROG
ಹ>@
3
3
3
5
5
5
3&'6
>V@