Parameter list   
7.2 Parameter list 
  SINAMICS V20 Inverter 
208  Operating Instructions, 07/2012, A5E03728167 
Parameter  Function  Range  Factory 
default 
Can be 
changed 
Scaling  Data 
set 
Data 
type 
Acc. 
Level 
  0  Disable 
  1  Fault 
  2  Warn 
P2361[0...2]    Cavitation threshold [%]  0.00 - 
200.00 
40.00  U, T  -  DDS  Float  2 
  Feedback threshold over which a fault / warning is triggered, as a percentage (%). 
P2362[0...2]    Cavitation protection 
time [s] 
0 - 65000  30  U, T  -  DDS  U16  2 
  The time for which cavitation conditions have to be present before a fault / warning is triggered. 
P2365[0...2]    Hibernation enable / 
disable 
0 - 1  0  U, T  -  DDS  U16  2 
  Enable or disable the hibernation functionality.  
0 = disabled 
1 = enabled 
P2366[0...2]    Delay before stopping 
motor [s] 
0 - 254  5  U, T  -  DDS  U16  3 
  With hibernation enabled. If the frequency demand drops below the threshold there is a delay of P2366 
seconds before the inverter is stopped. 
P2367[0...2]    Delay before starting 
motor [s] 
0 - 254  2  U, T  -  DDS  U16  3 
  With hibernation enabled. If pulses have been disabled by the unit going into hibernation, and the 
frequency demand has increased to above the hibernation threshold, there will be a delay of P2367 
seconds before the inverter restarts. 
P2370[0...2]    Motor staging stop mode  0 - 1  0  T  -  DDS  U16  3 
  Selects stop mode for external motors when motor staging is in use. 
  0  Normal stop 
  1  Sequence stop 
P2371[0...2]    Motor staging 
configuration 
0 - 3  0  T  -  DDS  U16  3 
  Selects configuration of external motors (M1, M2) used for motor staging feature. 
  0  Motor staging disabled 
  1  M1 = 1 x MV, M2 = Not fitted 
  2  M1 = 1 x MV, M2 = 1 x MV 
  3  M1 = 1 x MV, M2 = 2 x MV 
Caution:  For this kind of motor application it is mandatory to disable negative frequency setpoint! 
Note:  Motor staging allows the control of up to 2 additional staged pumps or fans, based on a PID control 
system. 
The complete system consists of one pump controlled by the inverter with up to 2 further pumps / fans 
controlled from contactors or motor starters. 
The contactors or motor starter are controlled by outputs from the inverter.