Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
42 Operating Instructions, 07/2012, A5E03728167
Connection macro Description
Display example
Cn007 External push button with analog setpoint
Cn008 PID control with analog input reference
Cn009 PID control with the fixed value reference
Cn010 USS control
Cn011 MODBUS RTU control
Setting connection macros
M
M
M
M
M
M
OK
OK
0RWRUGDWD
&RQQHFWLRQPDFUR
0LQXVVLJQVLJQLILHVFXUUHQW
VHOHFWHGPDFUR
$SSOLFDWLRQPDFUR
&XUUHQWVHOHFWHGPDFUR
V
&Q[[[
V
V
V
V
!V
V
!V

Connection macro Cn001 - BOP as the only control source
OK
OK
M
M
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1 + DO1 - P + N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V





N
)DXOW5XQQLQJ6SHHG
Connection macro settings:
Parameter Description Factory
default
Default for
Cn001
Remarks
P0700[0] Selection of command source 1 1 BOP
P1000[0] Selection of frequency 1 1 BOP MOP
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active
P0771[0] CI: Analog output 21 21 Actual frequency
P0810[0] BI: CDS bit 0 (Hand/Auto) 0 0 Hand mode