Commissioning   
5.5 Quick commissioning 
  SINAMICS V20 Inverter 
46  Operating Instructions, 07/2012, A5E03728167 
Parameter  Description  Factory 
default 
Default for 
Cn004 
Remarks 
P0732[0]  BI: Function of digital output 2  52.7  52.3  Inverter fault active 
Connection macro Cn005 - Analog input and fixed frequency 
The analog input works as an additional setpoint.  
●  If DI2 and DI3 are active together, the selected frequencies are summed, i.e. FF1 + FF2 
OK
M
10V  AI1  AI2   0V    DI1  DI2  DI3 DI4  DIC  24V  0V
AO + AO- DO1 +   DO1 - P +  N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
0~10 V=  
0~50/60Hz
N
212))
)L[HGVSHHGELW
)L[HGVSHHGELW
)DXOWDFNQRZOHGJHJPHQW
)DXOW5XQQLQJ6SHHG
   
 
Function diagram 
When the fixed speed is selected, the additional setpoint channel from the analog is 
disabled. If there is no fixed speed setpoint, the setpoint channel connects to the analog 
input.  
FF 01
FF 02
r1025
+
$QDORJLQSXW
$GGLWLRQDOVHWSRLQW
GLVDEOHG
)L[HGVSHHGV
6HWSRLQW
 
Connection macro settings: 
 
Parameter  Description  Factory 
default 
Default for 
Cn005 
Remarks 
P0700[0]  Selection of command source  1  2  Terminals as command source 
P1000[0]  Selection of frequency  1  23  Fixed frequency + analog setpoint 
P0701[0]  Function of digital input 1  0  1  ON / OFF 
P0702[0]  Function of digital input 2  0  15  Fixed speed bit 0 
P0703[0]  Function of digital input 3  9  16  Fixed speed bit 1