Commissioning   
5.5 Quick commissioning 
  SINAMICS V20 Inverter 
48  Operating Instructions, 07/2012, A5E03728167 
Parameter  Description  Factory 
default 
Default for 
Cn006 
Remarks 
P0732[0]  BI: Function of digital output 2  52.7  52.3  Inverter fault active 
P1040[0]  Setpoint of the MOP  5  0  Initial frequency 
P1047[0]  MOP ramp-up time of the RFG  10  10  Ramp-up time from zero to 
maximum frequency 
P1048[0]  MOP ramp-down time of the RFG  10  10  Ramp-down time from maximum 
frequency to zero 
Connection macro Cn007 - External push buttons with analog control 
Note that the command sources are pulse signals. 
OK
M
10V  AI1  AI2   0V    DI1  DI2  DI3 DI4  DIC  24V  0V
AO + AO- DO1 +   DO1 - P +  N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
0~10 V=  
0~50/60Hz
N
2))KROG
)RUZDUGSXOVH21
5HYHUVHSXOVH21
)DXOWDFNQRZOHGJHPHQWSXOVH
)DXOW5XQQLQJ6SHHG
   
 
2))
)RUZDUG
5HYHUVH
 
Connection macro settings: 
 
Parameter  Description  Factory 
default 
Default for 
Cn007 
Remarks 
P0700[0]  Selection of command source  1  2  Terminals as command source 
P1000[0]  Selection of frequency  1  2  Analog 
P0701[0]  Function of digital input 1  0  1  OFF hold 
P0702[0]  Function of digital input 2  0  2  Forward pulse + ON 
P0703[0]  Function of digital input 3  9  12  Reverse pulse + ON 
P0704[0]  Function of digital input 4  15  9  Fault acknowledgement