Commissioning 
  5.6 Function commissioning 
SINAMICS V20 Inverter 
Operating Instructions, 07/2012, A5E03728167 
71 
Setting parameters 
 
Parameter  Function  Setting 
P1230[0...2]  BI: Enable DC braking  This parameter enables DC braking via a signal applied from 
an external source. The function remains active while external 
input signal is active. 
Factory default: 0 
P1232[0...2]  DC braking current [%]  This parameter defines level of DC current relative to rated 
motor current (P0305). 
Range: 0 ... 250 (factory default: 100) 
P1233[0...2]  Duration of DC braking [s]  This parameter defines duration for which DC braking is active 
following an OFF1 or OFF3 command. 
Range: 0.00 ... 250.00 (factory default: 0.00) 
P1234[0...2]  DC braking start frequency [Hz]  This parameter sets the start frequency for DC braking. 
Range: 0.00 ... 599.00 (factory default: 599.00) 
P0347[0...2]  Demagnetization time [s]  This parameter changes time allowed after OFF2 / fault 
condition, before pulses can be re-enabled. 
Range: 0.000 ... 20.000 (factory default: 1.000) 
 
 
NOTICE 
 
The "DC braking" function is only practical for induction motors. 
DC braking is not suitable to hold suspended loads. 
For DC current braking, the motor kinetic energy is converted into thermal energy in the 
motor. If braking lasts too long, then the motor can overheat. 
While DC braking, there is no other way of influencing the inverter speed using an external 
control. When parameterizing and setting the inverter system, then as far as possible, it 
should be tested using real loads.