Controlled Power Module (CPM60.1)
A5E03975175-002, 04/2014
13
Mounting method
You mount the drive with four M5 screws to the inner wall of the cabinet. Note that the drive must be mounted vertically to
the cabinet wall, with the ventilation openings of the drive pointing upwards. The screw tightening torque of the drive must be
no more than 2.0 Nm.
Minimum mounting clearance
To ensure sufficient heat dissipation, please observe the requirements for minimum clearance between drives, one drive and
another device/inner wall of the cabinet, as illustrated in the picture below:
The use of supplied cable clamps
If the CE marking requirements for cables are mandatory, the mains input cable and the power cable used must all be
shielded type of cables. In that case, you can use the cable clamps as a ground connection between the cable shielding
layer and a common ground point.
Clamps can also be helpful in better fixing cables (the unshielded power cable and the mains input cable) in place.
The illustration below shows you how to use the clamps to fix both cables and to make a shielding connection with the cable.