Controlled Power Module (CPM60.1)
A5E03975175-002, 04/2014
37
This alarm may
occur when the
DC link is
connected
The rated torque is exceeded
1. check the load
2. lower the start/Stop
frequency
3. use drive and motor
with more power
maximum
energy or
torque)
The brake is not open Check whether the
brake is open or not
The motor is not stable
1. modify the gain
value
2. lessen load inertia
The encoder is wrongly wired Check the wiring
A45 The 65 enable signal is lost
when the motor is running
Check the 65 enable
terminal
Emergency
stop (the
motor will
stop with
the
maximum
energy or
torque)
Press the Enter key
on the operator
panel or terminal
RST of the X6
interface
Alarms with alarm code < A21 can be cancelled by power-on, while alarms with alarm code ≥ A21 can be cancelled by
RST terminal.
Errors during drive self-test
The drive module always conducts a self-test at every power-on. If any error occurs during this period, the drive screen form
will show one of the following error codes:
Error 1 RAM damaged Replace the drive
Error 2 Flash damaged Replace the drive
Error 3 Program copy error Replace the drive