Controlled Power Module (CPM60.1)
38 A5E03975175-002, 04/2014
1. Brake not open
– Description: The brake is not open when the drive is in "S-Run" state.
– Cause: A short circuit has occurred in the brake cable.
– Remedy: Check brake cable connection.
2. Axis position incorrect or axis does not move
– Description: When status display on SINAMICS V60 is "S-Run", the axis position is incorrect or the axis does not
move.
– Cause: Pin +PLUS or -PLUS is not well connected.
– Remedy: Check the cable connection on the pin +PLUS or -PLUS.
3. Axis does not move
– Description: When status display on SINAMICS V60 is "S-4", the axis does not move even the CNC controller has
sent out pulse signals.
– Cause: Pin +ENA or -ENA is not well connected.
– Remedy: Check the cable connection on the pin +ENA or -ENA.
4. Axis keeps running in a single direction
– Description: When status display on SINAMICS V60 is "S-Run", the axis corresponding keeps running in a single
direction no matter positive signals or negative signals are given.
– Cause: Pin +DIR or -DIR is not well connected.
– Remedy: Check the cable connection on the pin +DIR or -DIR.