Accessibility to "JOG" mode or "Save user parameter" mode (see the picture above) depends on the current display status
of the drive:
• When drive is in "S-4" (waiting for pulse enable) state, access to JOG mode is possible; alternatively, when the drive is
in "S-3" (waiting for 65 enable) state and P05 = 1, access to JOG mode is possible.
• Access to "Save user parameter" is possible as long as the drive is
in "S-Run" state or in "JOG-Run" mode.
• Please save modified parameters via the Store function in the function menu, otherwise, the parameter changes will be
lost if the drive is powered off. It must be noted that signal of servo enable (terminal X6-"65") or signal of pulse enable
(terminal X5-"+ENA"/"-ENA") should be cut off if you try to save the parameters; otherwise, "Forbid" (the saving action
is forbidden) will be displayed on the drive.
• The second default values are the default values of V01.06 or earlier.