Controlled Power Module (CPM60.1)
A5E03975175-002, 04/2014
23
Preconditions for display of normal status
S-2 Precharging the drive (waiting for the 220 V mains
power)
• No power supply (24 V DC) fault
• No alarm code appears
• No error code appears
S-3 Waiting for drive enable from terminal 65 at X6
• No power supply (24 V DC or 3AC 220 -
240 V) fault
• No alarm code appears
S-4 Waiting for pulse enable from terminals ENA+ and
ENA- at X5
• No power supply (24 V DC or 3AC 220-
240 V) fault
• No alarm code appears
• Terminal 65 has been enabled
S-RUN Drive is running properly
• No power supply (24 V DC or 3AC 220-
240 V) fault
• No alarm code appears
• Terminals 65 has been enabled via an
external 24 V DC power supply
• Terminals ENA+ and ENA- have been
enabled
S-A01
...
S-A45
Displays an alarm code associated with a fault
existent in the drive system
Descriptions of main keys:
Mode selection Switch between 4 main menu items (Status, Parameter Set, Data
Display and Function) or return current display to next higher-level.
Enter Go to next lower-level menu item or back to higher-level item, confirm
value (save modified value into RAM) or cancel an alarm.