Description
2.1 Mechanical components
3WJ Air Circuit breakers
16 Operating Instructions, 12/2022, L1V30828903001-01
2.1.4 Operation
2.1.4.1 Installation
Risk of equipment damage and/or personal injury
Before installing the Circuit breaker, make sure that the minimum distances from insulated,
grounded, and live components in the switchgear are observed.
Details can be found in the chapter Technical specifications (Page 196).
Installation position
Risk of equipment damage and/or personal injury
You must not install the withdrawable Circuit breaker tilted towards the frontside: The
Circuit breaker may slide out on the guiding rails, when racked in the disconnected position.