2.1 Mechanical components
3WJ Air Circuit breakers
Operating Instructions, 12/2022, L1V30828903001-01
21
2.1.4.3 Position of the Circuit Breaker in the guide frame
Diagram
Position and display
Main and auxiliary circuit
Cubicle door
Shutter
Maintenance position
Green
The auxiliary terminals of the
breaker are outside of the
auxiliary connector blocks of
the guide frame.
Open
Closed
Disconnect position
Green
The auxiliary terminals of the
breaker are inside the auxiliary
connector blocks of the guide
frame.
The guide rails are back in
their initial position.
Closed
Closed
Test position
Blue
Main circuits disconnected
Auxiliary circuits connected
Closed
Closed
Connected position
Red
Main circuits connected
Auxiliary circuits connected
Closed
Open
Main circuit
Auxiliary circuit
Shutter
Cubicle door