EasyManua.ls Logo

Siemens SINOVA - Inspection & Maintenance; Testing Withdrawable Breaker Functions and Auxiliary Circuits

Siemens SINOVA
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Inspection & Maintenance
4.4 Performing inspection
3WJ Air Circuit breakers
Operating Instructions, 12/2022, L1V30828903001-01
173
4.4.5 Testing of mechanical function of the withdrawable circuit breaker and the
guide frame
Note
The inspection of the withdrawable circuit breaker also includes all the items in Section
Testing of mechanical function of the circuit breaker (Page 172).
Check the following items:
Guide frame and racking mechanism including position indicator
Visual inspection of finger clusters for damage
Reliable function of control gate
Mechanical function:
Racking of circuit breaker
Opening of shutter
Function of position signaling switch module
Position indicator corresponds to actual position of circuit breaker
Release of racking mechanism interlock in the defined positions
Effectiveness of racking mechanism interlock in the intermediate positions
Coding of the withdrawable circuit breaker and the guide frame
4.4.6 Testing of auxiliary circuits
Check the following items:
Connections to the circuit breaker in accordance with circuit diagram:
Secure fitting
Correct terminal assignment
Withdrawable version: Auxiliary supply connector with sufficient tolerance for insertion in
the guide frame. Always correct rigid or non-flexible wiring.