Inspection & Maintenance
4.3 Planning of inspection and maintenance
3WJ Air Circuit breakers
170 Operating Instructions, 12/2022, L1V30828903001-01
4.3.3 Logging
Note
Obligation to maintain logs for warranty claims
The operator must log all inspection and maintenance work. The logs should be kept in the
archive for at least ten years.
In order to make it possible to clearly identify the circuit breaker and the general data, every
log should contain the following information:
General information:
Date of inspection/maintenance
Name of person responsible for inspection/maintenance
Names of other persons involved in inspection/maintenance
Date of last inspection/maintenance
Mounting location of the circuit breaker (room, power distribution equipment, section,
cell)
Ambient conditions (temperature, air humidity, pollution degree)
Field of application, sector
Special events during operation (e.g. short-circuit or overload trips)
Known fault scenarios in the past
Information about the circuit breaker:
Circuit breaker type
Article number and options
Circuit breaker ID number
ID number of electronic trip unit
Fixed-mounted or withdrawable version
Operating cycles recorded by means of mechanical operating cycles counter or
electronic trip unit
Information about inspection work performed